Article |
Specification |
Feature |
Load |
Rated heating capacity |
Calculate the heating load according to the customer's actual need (Heating water supply, or hot water supply) The user should count the largest load of each usage. |
Function |
Application |
Mansion.school.hotel, swimming pool.sauna center and any other places where hot and heating water supply is needed |
Fuel |
oil-fired |
Light oil |
Heat value: 10400kcal/kg |
Heavy oil |
Heat value: 10000kcal/kg |
gas-fired |
City gas |
Heat value (min): 3800kcal/nm3 |
Natural gas |
Heat value (min): 8500kcal/nm3 |
LPG |
Heat value (min): 25000kcal/nm3 |
Difference in temperature of heat-exchanger designed |
¡÷t=5¡æ(55¡æ-60¡æ) |
Heating water supply |
¡÷t=10¡æ(50¡æ-60¡æ) |
Heating water and hot water circulating supply
|
¡÷t=25¡æ) |
(60¡æ-85¡æ) |
Hot water and heating circulation for radiator
|
(45¡æ-70¡æ) |
Hot water and heating circulation for radiator
|
Fuel pipe size |
Oil fired vacuum boiler |
DN15 (<300,000kcal/h. DN20 (400.000kcal/h-1000.000kcal/h)
DN25 (>1000.000kcal/h) |
Gas fired vacuum boiler |
According to the actual gas heating value and its pressure |
Boiler's load
|
Standard style |
Pressure (max) 1.0MPa |
Allowed pressure style |
Pressure (max) 1.6MPa |
Special pressure style |
Pressure (max) 2.0Mpa |